Site icon Deco-Mep

Motor circuit breaker, TeSys GV2, 3P, 2.5-4 A, thermal magnetic, screw clamp terminals

Main
range
TeSys
product name
TeSys GV2
device short name
GV2ME
device application
Motor
trip unit technology
Thermal-magnetic
Complementary
poles description
3P
network type
AC
utilisation category
AC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2
network frequency
50/60 Hz conforming to IEC 60947-4-1
fixing mode
35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate)
operating position
Any position
motor power kW
1.1 kW at 400/415 V AC 50/60 Hz
1.5 kW at 400/415 V AC 50/60 Hz
1.5 kW at 500 V AC 50/60 Hz
3 kW at 690 V AC 50/60 Hz
2.2 kW at 500 V AC 50/60 Hz
2.2 kW at 690 V AC 50/60 Hz
breaking capacity
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
control type
Push-button
[In] rated current
4 A
thermal protection adjustment range
2.5…4 A
magnetic tripping current
51 A
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current
4 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-2
power dissipation per pole
2.5 W
mechanical durability
100000 cycles
electrical durability
100000 cycles for AC-3 at 440 V
maximum operating rate
25 cyc/h
rated duty
Continuous conforming to IEC 60947-4-1
tightening torque
1.7 N.m on screw clamp terminals
suitability for isolation
Yes conforming to IEC 60947-1
phase failure sensitivity
Yes conforming to IEC 60947-4-1
height
89 mm
width
45 mm
depth
78.5 mm
net weight
0.26 kg
Environment
standards
EN/IEC 60947-2
EN/IEC 60947-4-1
CSA C22.2 No 60947-4-1
UL 60947-4-1
product certifications
IECEE CB Scheme
UL
CSA
CCC
EAC
ATEX
BV
LROS (Lloyds register of shipping)
DNV-GL
RINA
protective treatment
TH
IP degree of protection
IP20 conforming to IEC 60529
IK degree of protection
IK04
ambient air temperature for operation
-20…60 °C
ambient air temperature for storage
-40…80 °C
fire resistance
960 °C conforming to IEC 60695-2-1
operating altitude
2000 m
Exit mobile version