range |
TeSys
|
|
---|---|---|
product name |
TeSys GV2
|
|
device short name |
GV2ME
|
|
device application |
Motor
|
|
trip unit technology |
Thermal-magnetic
|
poles description |
3P
|
|
---|---|---|
network type |
AC
|
|
utilisation category |
AC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2 |
|
network frequency |
50/60 Hz conforming to IEC 60947-4-1
|
|
fixing mode |
35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate) |
|
operating position |
Any position
|
|
motor power kW |
5.5Â kW at 400/415 V AC 50/60 Hz
7.5Â kW at 500 V AC 50/60 Hz 9Â kW at 690 V AC 50/60 Hz 11Â kW at 690 V AC 50/60 Hz |
|
breaking capacity |
100Â kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
3Â kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 15Â kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 8Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 6Â kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service short-circuit breaking capacity |
100Â % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
75Â % at 690 V AC 50/60 Hz conforming to IEC 60947-2 75Â % at 500 V AC 50/60 Hz conforming to IEC 60947-2 50Â % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50Â % at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
control type |
Push-button
|
|
[In] rated current |
14Â A
|
|
thermal protection adjustment range |
9…14 A
|
|
magnetic tripping current |
170Â A
|
|
[Ue] rated operational voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Ui] rated insulation voltage |
690Â V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Ith] conventional free air thermal current |
14Â A conforming to IEC 60947-4-1
|
|
[Uimp] rated impulse withstand voltage |
IEC 60947-2 6Â kV
|
|
power dissipation per pole |
2.5Â W
|
|
mechanical durability |
100000Â cycles
|
|
electrical durability |
100000Â cycles for AC-3 at 440 V
|
|
maximum operating rate |
25Â cyc/h
|
|
rated duty |
Continuous conforming to IEC 60947-4-1
|
|
tightening torque |
1.7Â N.m on screw clamp terminals
|
|
suitability for isolation |
Yes conforming to IEC 60947-1
|
|
phase failure sensitivity |
Yes conforming to IEC 60947-4-1
|
|
height |
89Â mm
|
|
width |
45Â mm
|
|
depth |
78.5Â mm
|
|
net weight |
0.26Â kg
|
standards |
EN/IEC 60947-2
EN/IEC 60947-4-1 CSA C22.2 No 60947-4-1 UL 60947-4-1 |
|
---|---|---|
product certifications |
IECEE CB Scheme
UL CSA CCC EAC ATEX BV LROS (Lloyds register of shipping) DNV-GL RINA |
|
protective treatment |
TH
|
|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
IK degree of protection |
IK04
|
|
ambient air temperature for operation |
-20…60 °C
|
|
ambient air temperature for storage |
-40…80 °C
|
|
fire resistance |
960 °C conforming to IEC 60695-2-1
|
|
operating altitude |
2000 m
|
Unit Type of Package 1 |
PCE
|
|
---|---|---|
Number of Units in Package 1 |
1
|
|
Package 1 Weight |
277Â g
|
|
Package 1 Height |
4.7Â cm
|
|
Package 1 width |
8.5Â cm
|
|
Package 1 Length |
9Â cm
|
|
Unit Type of Package 2 |
S02
|
|
Number of Units in Package 2 |
24
|
|
Package 2 Weight |
7.223Â kg
|
|
Package 2 Height |
15Â cm
|
|
Package 2 width |
30Â cm
|
|
Package 2 Length |
40Â cm
|
|
Unit Type of Package 3 |
P06
|
|
Number of Units in Package 3 |
384
|
|
Package 3 Weight |
122.148Â kg
|
|
Package 3 Height |
80Â cm
|
|
Package 3 width |
80Â cm
|
|
Package 3 Length |
60Â cm
|