TeSys D contactor – 4P(4 NO) – AC-1 – <= 440 V 25 A – 230 V AC 50/60 Hz coil
45,000 CFA
Ref: LC1DT25P7
SKU:
LC1DT25P7
Categories: Circuit breakers, Electrical
Description
range | TeSys | |
---|---|---|
product name | TeSys D | |
product or component type | Contactor | |
device short name | LC1D | |
contactor application | Resistive load | |
utilisation category | AC-1 | |
poles description | 4P | |
power pole contact composition | 4 NO | |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 25…400 Hz Power circuit: <= 300 V DC | |
[Ie] rated operational current | 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit | |
control circuit type | AC at 50/60 Hz | |
[Uc] control circuit voltage | 230 V AC 50/60 Hz | |
auxiliary contact composition | 1 NO + 1 NC | |
[Uimp] rated impulse withstand voltage | 6Â kV conforming to IEC 60947 | |
overvoltage category | III | |
[Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit 25 A (at 60 °C) for power circuit | |
Irms rated making capacity | 140Â A AC for signalling circuit conforming to IEC 60947-5-1 250Â A DC for signalling circuit conforming to IEC 60947-5-1 250Â A at 440 V for power circuit conforming to IEC 60947 | |
rated breaking capacity | 250Â A at 440 V for power circuit conforming to IEC 60947 | |
[Icw] rated short-time withstand current | 30 A 40 °C – 10 min for power circuit 61 A 40 °C – 1 min for power circuit 105 A 40 °C – 10 s for power circuit 210 A 40 °C – 1 s for power circuit 100 A – 1 s for signalling circuit 120 A – 500 ms for signalling circuit 140 A – 100 ms for signalling circuit | |
associated fuse rating | 10Â A gG for signalling circuit conforming to IEC 60947-5-1 40Â A gG at <= 690 V coordination type 1 for power circuit 25Â A gG at <= 690 V coordination type 2 for power circuit | |
average impedance | 2.5Â mOhm – Ith 25Â A 50 Hz for power circuit | |
[Ui] rated insulation voltage | Power circuit: 600Â V CSA certified Power circuit: 600Â V UL certified Signalling circuit: 690Â V conforming to IEC 60947-1 Signalling circuit: 600Â V CSA certified Signalling circuit: 600Â V UL certified Power circuit: 690Â V conforming to IEC 60947-4-1 | |
electrical durability | 0.8Â Mcycles 25Â A AC-1 at Ue <= 440 V | |
power dissipation per pole | 1.56Â W AC-1 | |
Front cover | With | |
mounting support | Plate Rail | |
standards | CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 | |
product certifications | UL BV CCC LROS (Lloyds register of shipping) DNV CSA RINA GOST GL | |
connections – terminals | Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Power circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end | |
tightening torque | Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2 Power circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm Power circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2 | |
operating time | 4…19 ms opening 12…22 ms closing | |
safety reliability level | B10d = 1369863Â cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000Â cycles contactor with mechanical load conforming to EN/ISO 13849-1 | |
mechanical durability | 15Â Mcycles | |
maximum operating rate | 3600 cyc/h 60 °C |
Additional information
Brand |
Schneider |
---|
Reviews (0)
Be the first to review “TeSys D contactor – 4P(4 NO) – AC-1 – <= 440 V 25 A – 230 V AC 50/60 Hz coil” Cancel reply