range |
TeSys
|
|
---|---|---|
product name |
TeSys D
|
|
product or component type |
Contactor
|
|
device short name |
LC1D
|
|
contactor application |
Resistive load
|
|
utilisation category |
AC-1
|
|
poles description |
4P
|
|
power pole contact composition |
4 NO
|
|
[Ue] rated operational voltage |
Power circuit: <= 690 V AC 25…400 Hz
Power circuit: <= 300 V DC |
|
[Ie] rated operational current |
40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
|
|
control circuit type |
AC at 50/60 Hz
|
|
[Uc] control circuit voltage |
230 V AC 50/60 Hz
|
|
auxiliary contact composition |
1 NO + 1 NC
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947
|
|
overvoltage category |
III
|
|
[Ith] conventional free air thermal current |
10 A (at 60 °C) for signalling circuit
40 A (at 60 °C) for power circuit |
|
Irms rated making capacity |
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1 450 A at 440 V for power circuit conforming to IEC 60947 |
|
rated breaking capacity |
450 A at 440 V for power circuit conforming to IEC 60947
|
|
[Icw] rated short-time withstand current |
50 A 40 °C – 10 min for power circuit
120 A 40 °C – 1 min for power circuit 240 A 40 °C – 10 s for power circuit 380 A 40 °C – 1 s for power circuit 100 A – 1 s for signalling circuit 120 A – 500 ms for signalling circuit 140 A – 100 ms for signalling circuit |
|
associated fuse rating |
10 A gG for signalling circuit conforming to IEC 60947-5-1
63 A gG at <= 690 V coordination type 1 for power circuit 40 A gG at <= 690 V coordination type 2 for power circuit |
|
average impedance |
2 mOhm – Ith 40 A 50 Hz for power circuit
|
|
[Ui] rated insulation voltage |
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified Power circuit: 690 V conforming to IEC 60947-4-1 |
|
electrical durability |
1.4 Mcycles 40 A AC-1 at Ue <= 440 V
|
|
power dissipation per pole |
3.2 W AC-1
|
|
Front cover |
With
|
|
mounting support |
Rail
Plate |
|
standards |
CSA C22.2 No 14
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
|
product certifications |
CCC
LROS (Lloyds register of shipping) RINA UL DNV BV CSA GL GOST |
|
connections – terminals |
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end Power circuit: connector 1 cable(s) 2.5…10 mm²flexible without cable end Power circuit: connector 2 cable(s) 2.5…10 mm²flexible without cable end Power circuit: connector 1 cable(s) 2.5…10 mm²flexible with cable end Power circuit: connector 2 cable(s) 2.5…10 mm²flexible with cable end Power circuit: connector 1 cable(s) 2.5…16 mm²solid without cable end Power circuit: connector 2 cable(s) 2.5…16 mm²solid without cable end |
|
tightening torque |
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2 Power circuit: 1.7 N.m – on connector – with screwdriver flat Ø 6 mm Power circuit: 1.7 N.m – on connector – with screwdriver Philips No 2 |
|
operating time |
4…19 ms opening
12…22 ms closing |
|
safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
|
mechanical durability |
15 Mcycles
|
|
maximum operating rate |
3600 cyc/h 60 °C
|