Vigi iC60 – earth leakage add-on block – 4P – 25A – 300mA – AC type

Main
range
Acti 9
product or component type
Add-on residual current devices
device short name
Vigi iC60
poles description
4P
[In] rated current
25 A
earth-leakage sensitivity
300 mA
earth-leakage protection time delay
Instantaneous
Earth leakage protection type
Type AC
network type
AC
network frequency
50/60 Hz
[Ue] rated operational voltage
400 V AC 50/60 Hz conforming to EN 61009-1
400/415 V AC 50/60 Hz conforming to IEC 61009-1
standards
EN 61009-1
IEC 61009-1
9 mm pitches
6
Complementary
device location in system
Outgoer
residual current tripping technology
Voltage independent
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
range compatibility
Acti 9 iC60
Acti 9 Reflex iC60
product compatibility
Single terminal
local signalling
Trip indicator
mounting mode
Clip-on
mounting support
DIN rail
electrical connection to mcb
By screws
comb busbar and distribution block compatibility
Bottom: YES
height
91 mm
width
54 mm
depth
73.5 mm
net weight
0.245 kg
connections – terminals
Tunnel type terminal downside for 1 cable(s) 1…25 mm² rigid without cable end
Tunnel type terminal downside for 1 cable(s) 1…16 mm² flexible without cable end
Tunnel type terminal downside for 1 cable(s) 1…16 mm² flexible with cable end
wire stripping length
14 mm for bottom connection
tightening torque
2 N.m bottom
Environment
IP degree of protection
IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529
pollution degree
3 conforming to IEC 60947-2
electromagnetic compatibility
8/20 µs impulse withstand, 250 A conforming to IEC 61009-1
ambient air temperature for operation
-5…60 °C
ambient air temperature for storage
-40…85 °C
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Weight
218 g
Package 1 Height
8.5 cm
Package 1 width
12 cm
Package 1 Length
14.7 cm
Exit mobile version