range |
Acti 9
|
|
---|---|---|
product or component type |
Add-on residual current devices
|
|
device short name |
Vigi iC60
|
|
poles description |
4P
|
|
[In] rated current |
63Â A
|
|
earth-leakage sensitivity |
300Â mA
|
|
earth-leakage protection time delay |
Instantaneous
|
|
Earth leakage protection type |
Type AC
|
|
network type |
AC
|
|
network frequency |
50/60 Hz
|
|
[Ue] rated operational voltage |
400 V AC 50/60 Hz conforming to EN 61009-1
400/415 V AC 50/60 Hz conforming to IEC 61009-1 |
|
standards |
EN 61009-1
IEC 61009-1 |
|
9 mm pitches |
7
|
device location in system |
Outgoer
|
|
---|---|---|
residual current tripping technology |
Voltage independent
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to IEC 60947-2
|
|
range compatibility |
Acti 9 iC60
Acti 9 Reflex iC60 |
|
product compatibility |
Single terminal
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
electrical connection to mcb |
By screws
|
|
comb busbar and distribution block compatibility |
Bottom: YES
|
|
height |
91Â mm
|
|
width |
135Â mm
|
|
depth |
73.5Â mm
|
|
net weight |
0.245Â kg
|
|
connections – terminals |
Tunnel type terminal downside for 1 cable(s) 1…35 mm² rigid without cable end
Tunnel type terminal downside for 1 cable(s) 1…25 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1…25 mm² flexible with cable end |
|
wire stripping length |
14Â mm for bottom connection
|
|
tightening torque |
3.5Â N.m bottom
|
IP degree of protection |
IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529 |
|
---|---|---|
pollution degree |
3 conforming to IEC 60947-2
|
|
electromagnetic compatibility |
8/20 µs impulse withstand, 250 A conforming to IEC 61009-1
|
|
ambient air temperature for operation |
-5…60 °C
|
|
ambient air temperature for storage |
-40…85 °C
|
Reviews
There are no reviews yet.