range of product |
Easypact CVS400…630
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
CVS400F
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
protected poles description |
3d
|
|
neutral position |
Left
|
|
Earth leakage protection (Vigi add on) |
Without
|
|
[In] rated current |
400 A at 40 °C
|
|
breaking capacity code |
F
|
|
network type |
AC
|
|
[Icu] Breaking capacity |
40Â kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
36Â kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
400 A at 40 °C
|
|
protection type |
Short-circuit protection (magnetic)
Overload protection (thermal) |
network frequency |
50/60 Hz
|
|
---|---|---|
control type |
Toggle
|
|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
connections – terminals |
Screw connection
|
|
[Uimp] rated impulse withstand voltage |
8Â kV conforming to EN/IEC 60947-2
|
|
thermal protection adjustment range |
280…400 A
|
|
[Ics] rated service breaking capacity |
40Â kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
36Â kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 23Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
mechanical durability |
15000Â cycles
|
|
electrical durability |
6000Â cycles 415 V In conforming to IEC 60947-2
|
|
connection pitch |
45Â mm
|
|
contact position indicator |
Yes
|
|
neutral protection setting |
No protection (3d)
|
|
long time pick-up adjustment type Ir |
Adjustable
|
|
long time pick-up adjustment range |
0.7…1 x In
|
|
long time delay adjustment type |
Fixed
|
|
instantaneous pick-up adjustment type Ii |
Adjustable
|
|
instantaneous pick-up adjustment range |
5…10 x In
|
|
height |
255Â mm
|
|
width |
185Â mm
|
|
depth |
110Â mm
|
|
net weight |
6.3Â kg
|
electrical shock protection class |
Class II
|
|
---|---|---|
standards |
EN 60947-2
IEC 60947-2 |
|
product certifications |
GOST
IEC |
|
IP degree of protection |
IP40
|
|
pollution degree |
3 conforming to IEC 60664-1
|
|
ambient air temperature for operation |
-25…70 °C
|
|
ambient air temperature for storage |
-50…85 °C
|
Unit Type of Package 1 |
PCE
|
|
---|---|---|
Number of Units in Package 1 |
1
|
|
Package 1 Weight |
6.53Â kg
|
|
Package 1 Height |
15.2Â cm
|
|
Package 1 width |
20.2Â cm
|
|
Package 1 Length |
29.2Â cm
|
Reviews