Circuit breaker EasyPact CVS400F, 36 kA at 415 VAC, 400 A rating thermal magnetic TM-D trip unit, 4P 3d
620,000 CFA
Ref: LV540309
SKU:
LV540309
Categories: Circuit breakers, Electrical
Description
| range of product | Easypact CVS400…630 | |
|---|---|---|
| product or component type | Circuit breaker | |
| device short name | CVS400F | |
| device application | Distribution | |
| poles description | 4P | |
| protected poles description | 3d | |
| neutral position | Left | |
| Earth leakage protection (Vigi add on) | Without | |
| [In] rated current | 400 A at 40 °C | |
| breaking capacity code | F | |
| network type | AC | |
| [Icu] Breaking capacity | 40Â kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36Â kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
| utilisation category | Category A | |
| trip unit name | TM-D | |
| trip unit technology | Thermal-magnetic | |
| trip unit rating | 400 A at 40 °C | |
| protection type | Short-circuit protection (magnetic) Overload protection (thermal) |
| network frequency | 50/60 Hz | |
|---|---|---|
| control type | Toggle | |
| mounting mode | Fixed | |
| mounting support | Backplate | |
| upside connection | Front | |
| downside connection | Front | |
| connections – terminals | Screw connection | |
| [Uimp] rated impulse withstand voltage | 8Â kV conforming to EN/IEC 60947-2 | |
| thermal protection adjustment range | 280…400 A | |
| [Ics] rated service breaking capacity | 40Â kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36Â kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 23Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
| mechanical durability | 15000Â cycles | |
| electrical durability | 6000Â cycles 415 V In conforming to IEC 60947-2 | |
| connection pitch | 45Â mm | |
| contact position indicator | Yes | |
| neutral protection setting | No protection (3d) | |
| long time pick-up adjustment type Ir | Adjustable | |
| long time pick-up adjustment range | 0.7…1 x In | |
| long time delay adjustment type | Fixed | |
| instantaneous pick-up adjustment type Ii | Adjustable | |
| instantaneous pick-up adjustment range | 5…10 x In | |
| height | 255Â mm | |
| width | 185Â mm | |
| depth | 110Â mm | |
| net weight | 6.3Â kg |
| electrical shock protection class | Class II | |
|---|---|---|
| standards | EN 60947-2 IEC 60947-2 | |
| product certifications | GOST IEC | |
| IP degree of protection | IP40 | |
| pollution degree | 3 conforming to IEC 60664-1 | |
| ambient air temperature for operation | -25…70 °C | |
| ambient air temperature for storage | -50…85 °C |
| Unit Type of Package 1 | PCE | |
|---|---|---|
| Number of Units in Package 1 | 1 | |
| Package 1 Weight | 6.53Â kg | |
| Package 1 Height | 15.2Â cm | |
| Package 1 width | 20.2Â cm | |