Miniature circuit-breaker, Acti9 iC60N, 2P, 16 A, C curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)
30,000 CFA
Ref: A9F79216
SKU:
A9F79216
Categories: Circuit breakers, Electrical
Description
| device application |
Distribution
|
|
|---|---|---|
| range |
Acti 9
|
|
| product name |
Acti 9 iC60
|
|
| product or component type |
Miniature circuit-breaker
|
|
| device short name |
IC60N
|
|
| poles description |
2P
|
|
| number of protected poles |
2
|
|
| [In] rated current |
16Â A
|
|
| network type |
AC
DC |
|
| trip unit technology |
Thermal-magnetic
|
|
| curve code |
C
|
|
| breaking capacity |
6000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 36Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
| utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
| suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
| standards |
EN 60898-1
IEC 60947-2 EN 60947-2 IEC 60898-1 |
| network frequency |
50/60 Hz
|
|
|---|---|---|
| magnetic tripping limit |
8 x In +/- 20 %
|
|
| [Ics] rated service breaking capacity |
15Â kA 75Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz 4.5Â kA 75Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz 15Â kA 75Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5Â kA 75Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5Â kA 75Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz 27Â kA 75Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz 27Â kA 75Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz 6000Â A 100Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz 6000Â A 100Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz 10Â kA 100Â % conforming to IEC 60947-2 – 72…125 V DC 10Â kA 100Â % conforming to EN 60947-2 – 72…125 V DC |
|
| limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
| [Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2 |
|
| [Uimp] rated impulse withstand voltage |
6Â kV conforming to EN 60947-2
6Â kV conforming to IEC 60947-2 |
|
| contact position indicator |
Yes
|
|
| control type |
Toggle
|
|
| local signalling |
Trip indicator
|
|
| mounting mode |
Fixed
|
|
| mounting support |
DIN rail
|
|
| comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
| 9 mm pitches |
4
|
|
| height |
85Â mm
|
|
| width |
36Â mm
|
|
| depth |
78.5Â mm
|
|
| net weight |
0.25Â kg
|
|
| colour |
White
|
|
| mechanical durability |
20000Â cycles
|
|
| electrical durability |
10000Â cycles
|
|
| connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
| wire stripping length |
14Â mm for top or bottom connection
|
|
| tightening torque |
2Â N.m top or bottom
|
|
| earth-leakage protection |